Analysis of Thermal Comfort in an Office Space Using Two Typical Ventilation Modes.
##plugins.themes.bootstrap3.article.main##
This study carried out a comparative study to evaluate the air-conditioning performance of an office space under two typical ventilation modes (displacement and mixing ventilation system). A wall supply diffuser is located at the ceiling height for the mixing ventilation case, whereas, the supply diffuser is at the floor level for the displacement ventilation case. In both cases, the exhaust grill is located at the ceiling. From the result of the simulation, the researchers observed that the displacement ventilation system could have a higher risk of discomfort relating to vertical temperature gradient than when compared to the mixing ventilation case. More so, the simulation result indicates that the temperature distribution in an office building is a function of the type of ventilation system adopted and marginally affected by the diffuser arrangement.
Downloads
Download data is not yet available.
References
-
. A. Noveselec and J. Srebic.2002. A critical review on the performance and design of combined cooled ceiling and displacement ventilation system. Energy and Building, [online] 34(5). pp 497-509.
Google Scholar
1
-
. Carrier “Air conditioning company,” Handbook of air conditioning system design,4th edition, McGraw-Hill, 1965.New York, USA.
Google Scholar
2
-
. D. Butler, Air conditioning using displacement ventilation to maximize free cooling. BRE, Watford,2012, pp. 1-20.
Google Scholar
3
-
. T. Sodec and R. Craig.1990. Under floor air supply system-The European experience. Ashrae Transactions.96 (2). pp.690-695.
Google Scholar
4
-
. G. Gan. 1996.Numerical Investigation of local discomfort in office with displacement ventilation. Fuel Energy.37 (2). pp. 82-157.
Google Scholar
5
-
. Q.Chen, P.Suter, A.Moser.1991. Influence of air supply parameters on indoor diffusion. Building Environ.26 (4). pp. 417-431.
Google Scholar
6
-
. BS EN ISO 7730. 1995.Moderate thermal environments-determining of the PMV and PPD indices and specification of the conditions for the thermal comfort. British standards Institute, London.
Google Scholar
7
Most read articles by the same author(s)
-
Chinedum Vincent Okafor,
U. John Ezeokonkwo,
Dominic Anosike Obodoh,
Peter Ogunoh,
Atmospheric Boundary Layer Simulation Using Wall Function Approach in OpenFoam CFD Software , European Journal of Engineering and Technology Research: Vol. 3 No. 2: FEBRUARY 2018 -
Chinedum Vincent Okafor,
Finite Element Analysis of Vortex Induced Responses of Multistory Rectangular Building , European Journal of Engineering and Technology Research: Vol. 3 No. 2: FEBRUARY 2018 -
Chinedum Vincent Okafor,
Kevin Chucks Okolie,
Mbanusi Echefuna Cyril,
Chinenye Pamela Okafor,
Analysis of Wind Effect on High-Rise Building for Different Terrain Category , European Journal of Engineering and Technology Research: Vol. 2 No. 12: DECEMBER 2017 -
Chinedum Vincent Okafor,
Finite Element Analysis of a Ribbed Roofing Panel under Static Flexure , European Journal of Engineering and Technology Research: Vol. 3 No. 6: JUNE 2018